General specifications
Product name
Eaton Moeller® series EASY I/O expansion
Part no.
EASY-E4-DC-4PE1
EAN
4015080892854
Product Length/Depth
58 millimetre
Product height
90 millimetre
Product width
36 millimetre
Product weight
0.1 kilogram
Certifications
IEC 60068-2-30
IEC 60664
EN 50178
IEC 60068-2-6
IEC 60068-2-27
IEC/EN 61000-6-2
EN 61010
IEC/EN 61000-6-3
CSA-C22.2 No. 61010
IEC/EN 61131-2
CULus per UL 61010
IEC/EN 61000-4-2
UL Category Control No.: NRAQ, NRAQ7
CE
UL File No.: E205091
DNV GL
UL Listed
UL hazardous location group D (propane)
UL hazardous location group B (hydrogen)
UL hazardous location division 2
UL hazardous location group A (acetylene)
UL hazardous location class I
UL hazardous location group C (ethylene)
Product Tradename
EASY
Product Type
I/O expansion
Product Sub Type
None
Features & Functions
Features
Additional measurement aids: Filtering (software), smoothing of analog input signal (PT1 behavior), only with set sampling time, selectable per sensor: yes
Expandable
Expansion device
Measuring principle: Two or three wire per sensor, selectable by connection of sensor
Functions
Card diagnostic
Diagnostics below lower measurement range
General information
Degree of protection
IP20
Insulation resistance
According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Mounting method
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Front build in possible
Overvoltage category
III
Pollution degree
2
Product category
Control relays easyE4
Protocol
TCP/IP
MODBUS
Residual ripple
≤ 5 %
Resolution
12 Bit (0- 4095, digital, scaling per sensor)
Software
EASYSOFT-SWLIC/easySoft7
Type
easyE4 extension
Voltage type
DC
Ambient conditions, mechanical
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
Horizontal
Vertical
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
Vibration resistance
57 - 150 Hz, 2 g constant acceleration
10 - 57 Hz, 0.15 mm constant amplitude
According to IEC/EN 60068-2-6
Climatic environmental conditions
Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Environmental conditions
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Relative humidity
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)
Electro magnetic compatibility
Air discharge
8 kV
Burst impulse
2 kV, Signal cable
According to IEC/EN 61000-4-4
2 kV, Supply cable
Contact discharge
6 kV
Electromagnetic fields
10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
10 V (according to IEC/EN 61000-4-6)
Radio interference class
Class B (EN 61000-6-3)
Surge rating
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
0.5 kV, Supply cables, symmetrical, EASY…DC, power pulses (Surge), EMC
1 kV, Supply cables, asymmetrical, power pulses (Surge), EMC
Voltage dips
20 ms
≤ 10 ms, Bridging voltage dips
Terminal capacities
Terminal capacity
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
0.2 - 4 mm² (AWG 22 - 12), solid
Screwdriver size
3.5 x 0.8 mm, Terminal screw
Tightening torque
0.6 Nm, Screw terminals
Electrical rating
Heat dissipation
3.4 W (at 24 V DC)
Inrush current
12.5 A (for 6 ms)
Power consumption
1 W
Power loss
1 W
Rated operational voltage
24 V DC (-15 %/+ 20 % - power supply)
20.4 - 28.8 V DC
Supply voltage at AC, 50 Hz - min
0 V AC
Supply voltage at AC, 50 Hz - max
0 V AC
Supply voltage at DC - min
20.4 V DC
Supply voltage at DC - max
28.8 V DC
Short-circuit rating
Short-circuit protection
≥ 1A (T), Fuse, Power supply
Communication
Connection type
Screw terminal
Cable
Cable length
≤ 30 m, unscreened, Analog inputs temperature resistance Pt100 or Ni1000 sensors
Input/Output
Input
Input type resistance sensor: Platinum sensor Pt100 (according to DIN EN 60751, IEC 751)
Input type resistance sensor: Nickel sensor Ni1000 (according to DIN 43760)
Input current
40 mA
Number of inputs (analog)
4
Number of inputs (digital)
0
Number of outputs (analog)
0
Number of outputs (digital)
0
Safety
Explosion safety category for gas
None
Potential isolation
Between Analog inputs PT100 or Ni1000 and Power supply: no
Between Analog inputs PT100 or Ni1000 and expansion units: yes
Between Analog inputs PT100 or Ni1000 and Inputs: no
Protection against polarity reversal
Yes, for supply voltage (Siemens MPI optional)
Explosion safety category for dust
None
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Programmable logic controllers PLC (EG000024) / Logic module (EC001417)
Electric engineering, automation, process control engineering / Control, Process Control System (PCS) / Programmable logic control (SPS) / Logic module (ecl@ss13-27-24-22-16 [AKE539019])
Supply voltage AC 50 Hz
0 - 0 V
Supply voltage AC 60 Hz
0 - 0 V
Supply voltage DC
20.4 - 28.8 V
Voltage type (supply voltage)
DC
Switching current
0 A
Power consumption
1 W
Number of analogue inputs
4
Number of analogue outputs
0
Number of digital inputs
0
Number of digital outputs
0
With relay output
No
Number of HW-interfaces industrial Ethernet
0
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
0
Number of HW-interfaces serial TTY
0
Number of HW-interfaces USB
0
Number of HW-interfaces parallel
0
Number of HW-interfaces wireless
0
Number of HW-interfaces other
0
With optical interface
No
Supporting protocol for EtherCAT
No
Supporting protocol for TCP/IP
Yes
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
No
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for Modbus
Yes
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
No
Radio standard Bluetooth
No
Radio standard WLAN 802.11
No
Radio standard GPRS
No
Radio standard GSM
No
Radio standard UMTS
No
IO link master
No
Redundancy
No
With display
No
Degree of protection (IP)
IP20
Basic device
No
Expandable
Yes
Expansion device
Yes
With time switch clock
No
Rail mounting possible
Yes
Wall mounting/direct mounting
Yes
Front built-in possible
Yes
Rack-assembly possible
No
Suitable for safety functions
No
SIL according to IEC 61508
None
Performance level according to EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Certified for UL hazardous location class I
Yes
Certified for UL hazardous location class II
No
Certified for UL hazardous location class III
No
Certified for UL hazardous location division 1
No
Certified for UL hazardous location division 2
Yes
Certified for UL hazardous location group A (acetylene)
Yes
Certified for UL hazardous location group B (hydrogen)
No
Certified for UL hazardous location group C (ethylene)
Yes
Certified for UL hazardous location group D (propane)
Yes
Certified for UL hazardous location group E (metal dusts)
No
Certified for UL hazardous location group F (carbonaceous dusts)
No
Certified for UL hazardous location group G (non-conductive dusts)
No
Width
36 mm
Height
90 mm
Depth
58 mm